Configuration - analog outputs: read and write, Analog output configuration parameters – Rockwell Automation 1420 PowerMonitor 500 User Manual
Page 57
Rockwell Automation Publication 1420-UM001D-EN-P - September 2013
57
PowerMonitor 500 Unit Data Tables
Appendix A
Table 27 - Configuration - Analog Outputs: Read and Write
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
304609
16
Analog output A0: parameters
configuration
CUSTOM
Refer to Table 28
304625
16
Analog output A1: parameters
configuration
CUSTOM
Table 28 - Analog Output Configuration Parameters
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
Block
address +0
1
Type of the variable that is linked to
the N analog output
UINT
Block
address +1
2
Minimum electric value of the N
analog output
REAL
Value min = 0
Value max = 9,999,000
Block
address +3
2
Maximum electric value of the N
analog output
REAL
Block
address +5
2
Minimum output value of the N
analog output
REAL
Value min = 0.0
Value max = 100.0
Block
address +7
2
Maximum output value of the N
analog output
REAL
Block
address +9
7 Reserved