List of connectable variables, Table 42, Isolation between inputs and outputs (1 minute) – Rockwell Automation 1420 PowerMonitor 500 User Manual

Page 69

Advertising
background image

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013

69

Technical Specifications

Appendix B

List of Connectable Variables

The variables listed in this table can be connected to the following items:

Analog outputs (all variables except energy values and run hour counter)
Pulse outputs (only energy values)
Alarm outputs (except energy, hour counter, and max values)

Housing DIN

Dimensions (WxHxD)

Module holder: 96 x 96 x 50 mm
‘A’ and ‘B’ type modules: 89.5 x 63 x 16 mm
‘C’ type module: 89.5 x 63 x 20 mm

Depth behind panel, max

81.7 mm

Material

ABS, self-extinguishing: UL 94 V-0

Mounting Panel

mounting

Pollution degree

2

Protection degree, front

(1)

IP65, UL type 4x indoor (NEMA4x indoor), UL type 12 (NEMA12), for use on flat surface of a Type 4X Indoor enclosure; for
use on flat surface of a Type 12 enclosure.

Protection degree, screw terminals

IP20

Weight, approx

400 g (0.88 lb) (packing included)

(1) Use with 60 or 70 °C copper conductor. Maximum surrounding air temperature 40 °C. The device shall be installed in a pollution degree 2 environment. Open Type Device. The terminals L1, L2, and L3 shall

be aquired by a circuit where devices or system, including filters or air gaps, are used to control overvoltages at the maximum rated impulse withstand voltage peak of 6.0 kV. Devices or system shall be
evaluated using the requirements in the Standard for Transient Voltage Surge Suppressors, UL 1449. Terminals tightening torque 0.79

N•m

(7 lb•in). The sum of the internal power consumption of the

assembled modules shall not be more than 5.3 W.

Table 40 - General Specifications

Attribute

Value

Table 41 - Power Supply Specification

Attribute

Value

Auxiliary power supply

90…260V AC/DC (48…62 Hz)

Power consumption

AC: 6 VA; DC: 3.5 W

Table 42 - Isolation Between Inputs and Outputs (1 minute)

Measuring Inputs

Relay Outputs

Communication

Port

Analog Outputs

Auxiliary Power

Supply

Measuring Inputs

-

4 kV

4 kV

4 kV

4 kV

Relay outputs

4 kV

2 kV

4 kV

4 kV

4 kV

Communication port

4 kV

4 kV

-

4 kV

4 kV

Analog Outputs

4 kV

4 kV

4 kV

0 kV

4 kV

Aux. power supply

4 kV

4 kV

4 kV

4 kV

-

TIP

Current inputs must be connected to external current transformers because the
isolation among the current inputs is just functional (100V AC).