PowerMonitor 500 EtherNet/IP Device Profile

Appendix C

Modbus TCP

The communication module supports Modbus TCP. The protocol is the same as

the PowerMonitor 500 unit with RS485 (Modbus RTU). Refer to

Chapter 4

for

protocol details. In this product, only one Modbus TCP connection (1 socket) is

allowed.

The EtherNet/IP and Modbus TCP do not run concurrently. If Modbus TCP

communication occurs, EtherNet/IP communication stops temporarily but

recovers in a minute or two.

ACD

If an address conflict is detected from the communication module, then the base

module displays ‘ACD Found’. In that case, it is necessary to check the network

configuration, resolve the problem, and then cycle control power to the power

monitor to re-establish communication.

TCP/IP Port

Default EtherNet/IP ports include the following:

UDP (implicit message): 2222 (0x08AE)
TCP (explicit message): 44818 (0xAF12)

You can reassign the default Modbus TCP port:502 (0x01F6).