PowerMonitor 500 Unit Data Tables

Summary of Data Tables

The Data Table Summary Index table summarizes all data tables available and

their general attributes.

Table 6 - Data Table Summary Index

Name of Data Table

Read

Write

Modbus Starting

Address

CIP Assy. Instance ID

(decimal)

No. of Elements Refer to Page

Product Information

X

300001

(1)

100

10

47

Real-time Metering Values (voltage and current)

X

300081

101

12

48

Real-time Metering Values (power, PF,
frequency)

X

300105

102

18

49

Maximum Metering Values (voltage and current)

X

300337

103

12

50

Maximum Metering Values (power, PF,
frequency)

X

300361

104

17

51

DMD Metering Values (voltage and current)

X

300849

105

12

52

DMD Metering Values (power, PF, frequency)

X

300873

106

17

53

Total and Partial Energy Meters - EtherNet/IP
Data Table

X

301281

107

9

54

Configuration - Base Unit: Read and Write

X

X

304097

-

79

55

Configuration - Alarms

X

X

Varies

-

16

56

Configuration - RS-485/RS-232 Communication

X

X

304356

-

17

56

Configuration - Analog Outputs: Read and Write

X

X

304609

-

32

57

Analog Output Configuration Parameters

X

X

Varies

-

16

57

Configuration - Digital Outputs: Read and Write

X

X

304865

-

12

58

Commands: Write-only

X

312369

-

45

59

Alarm and Output Status

X

316385

108

2

61

(1) To obtain the physical address, subtract 300001 from the Modbus address and convert the result to hexadecimal. Example: Physical address 0x000B corresponds to Modbus address 300012.