Unit Configuration

Chapter 3

80 DMD: This function lets you select the

calculation method of the DMD/AVG value of the

selected variable.

81 TYPE: select the type of Calculation mode to be

used for the DMD/AVG calculation.
FIXED: The instrument calculates the

AVG/DMD value of the measured variable over the

selected interval, updates the AVG/DMD value at

the end of the interval, then resets and starts a new

calculation.
SLIDE: When first configured, the instrument

calculates the AVG/DMD value and updates its

value at the beginning after the first selected

interval. After the first interval, the instrument

calculates the AVG/DMD value every minute,

generating a window whose width is the selected

interval and that moves forward every minute.

82 TIME: select the time interval for the DMD/

AVG calculation. Default is 15 minutes.

83 SYNC: select the Synchronization mode. That is

the method that controls the calculation method of

the average/demand according to the selected time.

110 FILTER: The digital filter makes it possible to

stabilize the display of fluctuating measurements.

See

Digital Filtering Operation on page 30

.

111 FILTER S: set the operating range (span) of the

digital filter. The value is expressed as a % (filter to

0.0 means filter excluded).

112 FILTER CO: set the filtering coefficient of the

instantaneous measures. By increasing the value, also

the stability and the settling time of the measures are

increased.
IMPORTANT: Some specific menus display only if

the relevant modules are installed.

Where:

Pmax is the maximum power

Pc is the contractual power

t1 is the selected time period for the calculation of the AVG/DMD value

Page 9