Publication 1734-UM002C-EN-P - July 2003

D-6 Default Data Maps

1734-OW2 Relay Sink/Source Output Module

Message size: 1 Byte

1734-OX2 Relay Output Module

Message size: 1 Byte

1734-IE2C Analog Current Input Module

Message size: 6 Bytes

7

6

5

4

3

2

1

0

Consumes (scanner Tx)

Not used

Ch1

Ch0

Channel state

Where: 0 = OFF 1 = ON

7

6

5

4

3

2

1

0

Consumes (scanner Tx)

Not used

Ch1

Ch0

Channel state

Where: 0 = NO contact OFF, NC contact ON1 = NO contact ON, NC contact OFF

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces (scanner Rx)

Input Channel 0 High Byte

Input Channel 0 Low Byte

Input Channel 1 High Byte

Input Channel 1 Low Byte

Status Byte for Channel 1

Status Byte for Channel 0

OR

UR

HHA LLA

HA

LA

CM

CF

OR

UR

HHA LLA

HA

LA

CM

CF

Consumes
(scanner Tx)

No consumed data

Where: CF = Channel Fault status0 = no error1 = fault

CM = Calibration Mode0 = normal1 = calibration mode
LA = Low Alarm0 = no error1 = fault
HA = High Alarm0 = no error1 = fault
LLA = Low/Low Alarm0 = no error1 = fault
HHA = High/High Alarm0 = no error1 = fault
UN = Underrange0 = no error1 = fault
OR = Overrange0 = no error1 = fault