Publication 1734-UM002C-EN-P - July 2003

B-8 1734-ADNX Quick Start

If you are not going to use the subnet, you must still terminate it!
You can use the connector provided with the 1734-ADNX and
connect two resistors between the white and blue positions.

• Termination resistors are 121 Ohms, 1/4 Watt, 1%, Rockwell

part number 1785A-C2.

• Do not use carbon resistors. Metal film is recommended.

Continue ONLY after You have verified that the taps are
terminated correctly.

20. Double click on the 1734-ADNX to open the properties window.

In the next step you will download the EDS defaults to the
1734-ADNX.

21. Select the parameter tab and choose Download.

20475w-res