B-2 1734-ADNX Quick Start

The new Subnet system attributes include:

• Most field devices are more than 100m from the ControlLogix

Processor

• Previously installed and documented at 500 Kbaud
• 1734-ADNX with discrete inputs and outputs for several field

devices

• DeviceNet Starter Auxiliary (DSA)
• DeviceNet RightSight Photoelectric Sensor
• The ability to be replicated several times in the future without

changing documentation. (i.e., devices will be replicated with
same attributes, node addresses, etc.)

The existing devices will be wired to POINT I/O. The DSA and
RightSight will be connected to the 1734-ADNX on the 1734-ADNX’s
subsystem. This will allow them to run at the 500 Kbaud rate of the
Subnet, at more than 100m from the ControlLogix Processor.

NetLinx will let you configure everything from your PC, using the
1756-ENBT module and a 1756-DNB. You will be able to connect
from your computer over Ethernet to the ControlLogix backplane and
configure both the primary (remember the 1734-ADNX will be a new
node on this network) and Subnet network (the 1734-ADNX will be
node 0 on this network).

When you have completed this exercise, you will be able to browse
through the 1734-ADNX to see its backplane and the DSA and
RightSight, using only the RSNetWorx for DeviceNet software package.

1. Open RSNetWorx for DeviceNet by double clicking the icon on

your desktop.

2. From the RSNetWorx for DeviceNet main menu select File>New.