What is the 1734-ADN(X) Adapter? 2-7

• Collects I/O data from the Subnet and sends it to devices on the

DeviceNet network (e.g., scanners or controllers)

• Supplies power to the backplane I/O modules (See Appendix A

for power supply rules regarding I/O modules power
requirements.)

Data Collection

The adapter collects I/O data from up to 63 modules via the Subnet.
The I/O modules appear on the primary DeviceNet network as a
single node, though, and require only one DeviceNet node address.

Module Power

The adapter supplies 5V logic power to POINT I/O modules by
converting 24V dc field power to PointBus 5V power.

You can connect up to 63 I/O modules to each adapter, and you can
power to the backplane I/O modules from the adapter (with a
maximum of 10A of field power). You may use the integrated, isolated
24V dc expansion power unit (1734-EP24DC) to power additional I/O
modules, as shown below.

IMPORTANT

If Automatic Device Replacement (ADR) is enabled
on the adapter, you can only connect up to 62
modules via the Subnet.