Set subnet/backplane baudrate, Set subnet i/o module addresses – Rockwell Automation 1734-ADNX POINT I/O DeviceNet Adpater User Manual User Manual

Page 23

Advertising
background image

Publication 1734-UM002C-EN-P - July 2003

What is the 1734-ADN(X) Adapter? 2-3

Set Subnet/Backplane Baudrate

The adapter and Subnet modules must use the same baudrate to
communicate with each other. Use one or both of the following to set
a Subnet baudrate.

• Enable or disable the Backplane Autobaud feature for POINT

I/O modules. POINT I/O modules have Autobaud enabled as
the default- See page 2-12.

• Set the adapter baudrate for the Subnet. The default for the

1734-ADN is 1Mbaud. The default for the 1734-ADNX is
125Kbaud - See page 2-9.

Set Subnet I/O Module Addresses

Once the adapter and POINT I/O modules are communicating at the
same rate on the backplane, you must make sure all modules use a
valid MAC ID.

Set the Auto Address feature for POINT I/O modules - See

page 2-13.

IMPORTANT

You set the backplane baudrate for the 1734-ADN.
You set the Subnet baudrate for the 1734-ADNX.