Publication 1734-UM002C-EN-P - July 2003

Default Data Maps

D-7

Channel Status

1734-IE2V Analog Input Module

Message size: 6 Bytes

Table

D.A

Channel Status Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Over Range

Under Range

High High Alarm

Low Low Alarm

High Alarm

Low Alarm

CAL Mode

Channel Fault

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces (scanner Rx) Input Channel 0 - High Byte

Input Channel 0 - Low Byte

Input Channel 1 - High Byte

Input Channel 1 - Low Byte

Status Byte for Channel 1

Status Byte for Channel 0

OR

UR

HHA

L
LA

HA

LA

CM

CF

OR

UR

HHA

L
LA

HA

LA

CM

CF

Consumes (scanner
Tx)

No consumed data

Where: CF = Channel Fault status; 0 = no error, 1 = fault

CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault

Advertising