Rockwell Automation 1734-ADNX POINT I/O DeviceNet Adpater User Manual User Manual

Page 17

Advertising
background image

Publication 1734-UM002C-EN-P - July 2003

Installing the 1734-ADN(X) Adapter 1-3

4. Set the node address using the 2-position thumbwheel switch.

Valid physical settings range from 00 to 63. Press either the + or
- buttons to change the number.

You can also set the node address to some value between 64-99.
In this case, you can change the adapter’s node address via the
RSNetWorx for DeviceNet software. If a value between 64-99 is
used, at power-up the node address stored in the adapter’s
non-volatile memory is used.

5. Slide the safety end cap up to remove it. This exposes the

backplane and power interconnections.

Adapter
Status

DeviceNet
Status

PointBus
Status

1734-ADN

Field
Power

System
Power

Network Node
Address Thumbwheel

42510

31112-MC

Safety end cap

ATTENTION

!

Do not discard the safety end cap. Use this end cap
to cover the exposed interconnections on the last
mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from
electric shock.