3-2 Using Auto Start Mode

Why Use Auto Start Mode?

Auto Start Mode offers you a quick and easy method of getting your
POINT I/O system ‘up and running’. If your POINT I/O application
can use default configuration, you should use Auto Start Mode to
easily begin operations.

Once your adapter is:

• installed
• connected to the system’s I/O modules
• online (in RSNetWorx for DeviceNet)

you only need to choose the Auto Start Mode option and the adapter
begins working with a default configuration.

What Does Auto Start Mode Do?

When using Auto Start Mode, the adapter:

1. Sets all modules on the backplane to Auto Baud.

2. Reads the Subnet module’s identity information.

3. Sets backplane modules’ addresses sequentially.

4. Generates a scanlist for the Subnet.

5. Maps I/O data, based on byte, word, double-word, or fixed

boundaries.

When this sequence of events is completed, the POINT I/O modules
connected to the adapter are ready to accept connections from a
scanner.

IMPORTANT

Although Auto Start Mode allows your adapter to
operate with a default configuration, you can write a
custom configuration after operation has begun.

For more information on how to write custom
configuration for your adapter on DeviceNet, see
Chapter 5, Adding the 1734-ADN(X) to the
DeviceNet Scanner’s Scanlist
.