Hardware features, 1–2 overview, Dip switches – Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 12

Advertising
background image

1–2

Overview

Publication 1746Ć6.8 - April 1997

Important: Status words are only available when the module is

configured for Class 3.

Hardware Features

The module fits into any slot, except the processor slot (0), in either
an SLC 500 modular system or an SLC 500 fixed system expansion
chassis (1746-A2).

The module contains a removable terminal block providing
connection for eight analog input channels, which is specifically
designed to interface with analog current and voltage input signals.
The channels can be wired as either single-ended or differential
inputs. There are no output channels on the module. Module
configuration is done via the user program. There are DIP switches
on the circuit board for selecting voltage or current input.

Voltage

Current

O

Cable Tie Slots

SelfĆLocking Tabs

Side Label

Removable

Terminal Block

SHIELD

SHIELD

CHL3-

CHL3+

CHL2-

CHL2+

CHL1-

CHL1+

CHL0-

CHL0+

Door Label

Channel Status

LEDs (Green)

Module Status

LED (Green)

CHL7-

CHL6-

CHL5-

CHL4-

CHL7+

CHL6+

CHL5+

CHL4+

INPUT

CHANNEL STATUS

ANALOG

0

1

2

3

4

5

6

7

MODULE STATUS

2

1

N

DIP

Switches

Voltage

Current

O

2

1

N

Voltage

Current

O

2

1

N

Voltage

Current

O

2

1

N

Hardware Feature

Function

Channel Status LED Indicators

Displays channel operating and fault status.

Module Status LED

Displays module operating and fault status.

Side Label (Nameplate)

Provides module information.

Removable Terminal Block

Provides physical connection to input devices.

Door Label

Permits easy terminal identification.

Cable Tie Slots

Secures and route wiring from module.

SelfĆLocking Tabs

Secures module in chassis slot.

Voltage/current Selection DIP Switches

Selects voltage or current input type to match the analog sensor.

Advertising