Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 71

Advertising
background image

8–6

Application Examples

Publication 1746Ć6.8 - April 1997

Channel Configuration Worksheet

(With Settings Established for Channels 0-4)

Input Type

Data Format

Open Circuit

Filter Frequency

Channel Enable

Not Used

Channel 0 - N10:0

Channel 1 - N10:1

Channel 2 - N10:2

Channel 3 - N10:3

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙ

11

12

13

14

15

0

0

0

0

9

10

8

6

7

4

5

0

1

2

3

0

0

0

0

0

0

0

0

0

0

0

0

Bit Number

Channel 4 - N10:4

Channel 5

Channel 6

Channel 7

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0

1

0

0

0

1

0

0

0

0

1

0

1

1

0

0

0

1

0

0

0

0

1

1

0

1

0

0

0

1

0

0

0

0

1

1

0

1

0

0

0

1

0

0

0

0

1

1

0

1

0

0

0

1

0

0

0

0

Bit Definitions:

Bits 0-2

Input Type

000 =

±

10V dc

001 = 1-5V dc

010 = 0-5V dc

011 = 0-10V dc

100 = 0-20 mA

101 = 4-20 mA

110 =

±

20 mA

111 = 0-1 mA

Bits 3- 5

Data Format

000 = engineering units

001 = scaledĆforĆPID

010 = proportional counts

011 = 1746ĆNI4 data format

100 = user defined scaling

101 = user defined scaling

110 = illegal

111 = illegal

Bits 6 and 7

Open Circuit

00 = zero

01 = upscale

10 = downscale

11 = illegal

Bits 8-10

Filter Frequency 000 = no filter

001 = 75 Hz

010 = 50 Hz

011 = 20 Hz

100 = 10 Hz

101 = 5 Hz

110 = 2 Hz

111 = 1 Hz

Bit 11

Channel Enable

0 = channel disabled

1 = channel enabled

Bits 12-15

Not Used

0000 = always make this setting

The open circuit option is only valid for the 4-20 mA data format.

Advertising