4–4

Preliminary Operating Considerations

Publication 1746Ć6.8 - April 1997

Example – If you want to configure channel 2 on the analog module
located in slot 4 in the chassis, your address would be O:4.2.

O : 4 . 2

File Type

Slot

Word

Element

Delimiter

Word

Delimiter

Chapter 5, Channel Configuration, Data, and Status, gives you
detailed bit information about the data content of the configuration
word.

Input Image - Data Words and Status Words

The input image (defined as the input from the module to the
processor) represents data words and status words.

Important: Status words are only available when the module is

configured for Class 3.

Input words 0–7 (data words) hold the input data that represent the
value of analog inputs for channels 0–7. This data word is valid only
when the channel is enabled and there are no channel errors.

Input words 8–15 (status words) contain the status of channels 0–7
respectively. The status bits for a particular channel reflect the
configuration settings that you entered into the output image
configuration word for that channel and provide information about
the channel’s operational state. To receive valid status information
the channel must be enabled, and the channel must have processed
any configuration changes that may have been made to the
configuration word.

Example – To obtain the status of channel 2 (input word 10) of the
analog module located in slot 4 in the SLC chassis, use address
I:4.10.

I : 4 . 10

File Type

Slot

Word

Element

Delimiter

Word

Delimiter

Chapter 5, Channel Configuration, Data, and Status, gives you
detailed bit information about the content of the data word and the
status word.