Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 50

Advertising
background image

5–9

Channel Configuration, Data, and Status

Publication 1746Ć6.8 - April 1997

Scaled-for-PID to “Real” Units

Situation: A transducer is being used to measure temperature.

The 4–20 mA signal is proportional to 100–500

°

C (212–932

°

F).

The channel data word is in scaled-for-PID format.
The channel data = 5500.

Find: “Real” units equivalent in

°

F.

Equation:

Real Units Equivalent + S

LOW

)

ƪ

(S

HIGH

* S

LOW

)

ǒ

channel data value

full scale default PID value

Ǔ

ƫ

where: S

LOW

= 212

°

F

S

HIGH

= 932

°

F

channel data word = 5500
full scale PID default value (from table on page

5–6) = 16383

Solution:

RealăUnitsăEquivalent + 212°F )

ƪ

(932°F * 212°F)

ǒ

5500

16383

Ǔ

ƫ

+ 453.71°F

Proportional Counts to “Real” Units

Situation: A transducer is being used to measure pressure.

The –10V dc to +10V dc signal is proportional to 0 to 200 psi.
The channel data word is in proportional counts data format.
The channel data = 21567.

Find: “Real” units equivalent in psi.

Equation:

Real Units Equivalent + S

LOW

)

ƪ

(S

HIGH

* S

LOW

)

ǒdata value ) Ť proportional count low default valueŤāǓ

ǒproportional count full scale default valueǓ

ƫ

where: S

LOW

= 0 psi

S

HIGH

= 200 psi

channel data = 21567
proportional count low default value (from table on page 5–6) = –32768
proportional count full scale default value (from table on page

5–6) = 65535

Solution:

Real Units Equivalent + 0 psi )

ƪ

ǒ200 psi * 0 psiǓ

ǒ21567 ) Ť -32678ŤāǓ

(65535)

ƫ

+ 165.55 psi