4 - preliminary operating considerations, Module id code, Preliminary operating considerations – Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 32: Chapter

Advertising
background image

Chapter

4

Publication 1746Ć6.8 - April 1997

Preliminary Operating

Considerations

This chapter explains how the analog input module and the SLC 500
processor communicate through the module’s input and output
image. It lists the preliminary setup and operation required before
the module can function in a 1746 I/O system. Topics discussed
include how to:

enter the module ID code

select the Class 1 or Class 3 interface

address your 1746-NI8 module

select the proper input filter for each channel

calculate the module update time

interpret the module response to slot disabling

The module identification code is a unique number encoded for each
1746 I/O module. The code defines for the processor the type of I/O
or specialty module residing in a specific slot in the 1746 chassis.

Catalog Number

ID Code

1746ĆNI8

3526 - Class 1 interface

12726 - Class 3 interface

Important: All programming software does not support

configuration for Class 3 operation.

Advanced Programming Software (APS) supports Class 3
configuration. After entering the ID code (12726), enter 16 input
words and 12 output words.

SLC 500 A.I. Series

t Programming Software supports Class 3

configuration. After entering the ID code (12726), enter 16 input
words and 12 output words.

RSLogix 500

t, version 1.30 or later, supports Class 3

configuration. After entering the ID code (12726), select Class 3
operation.

Earlier versions of RSLogix 500 will only support configuration
for Class 1 operation. Contact Rockwell Software for
information on upgrading your software.

Module ID Code