Monitoring channel status bits, Monitoring channel status bits (class 3 mode only) – Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 59

Advertising
background image

6–4

Ladder Logic Configuration Examples

Publication 1746Ć6.8 - April 1997

This example shows how you could monitor the open circuit error
bits of each channel and set an alarm in the processor if one of the
channels opens. An open circuit error can occur if the analog input
device breaks, or one of the sensor wires gets cut or disconnected
from the terminal block.

Program Listing

] [

Copy File
Source

#N10:0

Dest

#O:3.0

Length

8

First Pass Bit

S2:1

15

COP

Initialize 1746ĆNI8

11

Channel 0

Status

] [

I:3.8

] [

I:3.8

12

( )

O:2.0

0

Channel 0

Open

Channel 0

Alarm

11

Channel 1

Status

I:3.9

12

( )

O:2.0

1

Channel 1

Open

Channel 1

Alarm

I:3.9

] [

] [

11

Channel 7

Status

I:3.15

] [

I:3.15

12

( )

O:2.0

7

Channel 7

Open

Channel 7

Alarm

] [

END

DATA FILE N10

Offset

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

N10:0

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:1

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:2

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:3

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:4

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:5

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:6

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

N10:7

0

0

0

0

1

1

0

0

0

0

0

0

1

1

0

1

Monitoring Channel Status

Bits (Class 3 Mode Only)

Advertising