Channel Configuration, Data, and Status

Publication 1746Ć6.8 - April 1997

Channel 0-7 Status Word (I:e.8 through I:e.15) - Bit Definitions

Bit(s)

Define

These bit settings

Indicate this

Bit(s)

Define

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Indicate this

0

0

0

"

10 V dc

0

0

1

1-5V dc

0

1

0

0-5V dc

0 2

Input Type

0

1

1

0-10V dc

0-2

Input Type

1

0

0

0-20 mA

1

0

1

4-20 mA

1

1

0

"

20 mA

1

1

1

0-1 mA

0

0

0

Engineering Units

0

0

1

ScaledĆforĆPID

0

1

0

Proportional Counts

3-5

Data Format

0

1

1

1746ĆNI4 Data Format

3-5

Data Format

1

0

0

User Defined (Class 3)

1

0

1

User Defined (Class 3)

ЙЙЙ

ЙЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

Illegal (configuration error)

ЙЙЙ

ЙЙ

ЙЙ

ЙЙЙЙЙЙЙЙ

Illegal (configuration error)

0

0

Zero

6 and 7

Open Circuit

0

1

Upscale

6 and 7

Open Circuit

1

0

Downscale

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙЙЙЙЙЙЙ

ЙЙЙЙЙЙЙЙ

Illegal (configuration error)

0

0

0

No Filter

0

0

1

75 Hz

0

1

0

50 Hz

8 10

Filter

0

1

1

20 Hz

8-10

Filter

Frequency

1

0

0

10 Hz

q

y

1

0

1

5 Hz

1

1

0

2 Hz

1

1

1

1 Hz

11

Channel

0

Channel Disabled

11

Channel

Status

1

Channel Enabled

12

Open Circuit

0

No Error

12

Open Circuit

Error

1

Open Circuit Detected

13

OverĆRange

0

No error

13

Over Range

Error

1

OverĆRange Condition

14

UnderĆRange

0

No Error

14

Under Range

Error

1

UnderĆRange Condition

15

Configuration

0

No Error

15

Configuration

Error

1

Configuration Error

Important: If the channel for which you are seeking status is

disabled (bit O:e.x/11 = 0), all bit fields are cleared.
The status word for any disabled channel is always
0000 0000 0000 0000 regardless of any previous setting
that may have been made to the configuration word.