Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 19

Advertising
background image

2–5

Quick Start

Publication 1746Ć6.8 - April 1997

1746ĆNI8 Module Output Image - Channel Configuration

Class 1

Class 3

O:1.0

channel 0 configuration word

bit mapped field

O:1.1

channel 1 configuration word

bit mapped field

O:1.2

channel 2 configuration word

bit mapped field

O:1.3

channel 3 configuration word

bit mapped field

O:1.4

channel 4 configuration word

bit mapped field

O:1.5

channel 5 configuration word

bit mapped field

O:1.6

channel 6 configuration word

bit mapped field

O:1.7

channel 7 configuration word

bit mapped field

O:1.8

lower scale limit range 0

16 bit integer

O:1.9

upper scale limit range 0

16 bit integer

O:1.10

lower scale limit range 1

16 bit integer

O:1.11

upper scale limit range 1

16 bit integer

8.

Program the configuration.

Reference

Do the programming necessary to establish the new configuration word setting in the previous step.

1. Create integer file N10. Integer file N10 should contain one element for each channel used.

(For this example we only need one, N10:0.)

2. Enter the configuration parameters from step 7 for channel 0 into integer N10:0.

3. Program an instruction in your ladder logic to copy the contents of N10:0 to output word O:1.0.

Chapter 6

(Ladder Logic

Configuration

Examples)

Chapter 8

(Application

Examples)

On power up, the first pass bit

(S:1/15) is set for one scan, enabling

the COPY instruction that transfers

the channel configuration word 0.

This configures and enables the

channel.

DATA FILE N10

Offset

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

N10:0

0

0

0

0

1

0

1

1

0

0

0

0

0

0

0

0

] [

COP

COPY FILE
Source

#N10:0

Dest

#O:1.0

Length

1

First Pass Bit

S:1

15

Initialize 1746ĆNI8