Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 29

Advertising
background image

3–8

Installation and Wiring

Publication 1746Ć6.8 - April 1997

Wiring Schematic for SingleĆended Analog Input Connections

Transmitter

+

Transmitter

Supply

Signal

+

IN 1 +
IN 1 -

IN 3 +

IN 3 -

+

Power

Supply

-

IN 0 +
IN 0 -

IN 2 +
IN 2 -

Transmitter

+

Signal

Transmitter

+

Signal

Ground

NI8

Signal

When wiring singleĆended analog

input devices to the analog input

module, the number of total wires

necessary can be limited by

jumpering all IN-" terminals

together. Note that differential

inputs are more immune to noise

than singleĆended inputs.

Important: The module does

not provide loop power for

analog inputs. Use a power

supply that matches the

transmitter specifications.
Important: Follow the

guidelines on pages 3-

7

and

3-9

when wiring the module.

Wiring Schematics for 2, 3, and 4ĆWire Analog Input Devices

2ĆWire Transmitter

Transmitter

+

-

4ĆWire Transmitter

Transmitter

Supply

Signal

+
-

+

-

IN +

IN -

Module

IN +
IN -

Module

+

Power

Supply

-

+

Power

Supply

-

Important: The module does

not provide loop power for

analog inputs. Use a power

supply that matches the

transmitter specifications.
Important: Follow the

guidelines on pages

3-7 and

3-9 when wiring the module.

3ĆWire Transmitter

Transmitter

Supply

Signal

GND

IN +

IN -

Module

+

Power

Supply

-

Advertising