Application Examples

Publication 1746Ć6.8 - April 1997

Program Set Up and Operation Summary

1. Set up one configuration word in memory for each channel. The

table below shows the configuration word allocation summary.

Channel

Configuration Word

Value

0

N10:0

L1 (amps)

1

N10:1

L2 (amps)

2

N10:2

L3 (amps)

3

N10:3

pressure (psi)

4

N10:4

liquid level (inches)

2. When the position of the three-position selector changes, convert

the appropriate scaled data word to BCD and send the data to the
LED display.

Amps

High Level

Display Panel

L1

Selector Switch

L1 - I:6/0

L2 - I:6/1

L3 - I:6/2

Liquid Level

PSI

Low Level

L3

L2

3. If the liquid level goes below the low level set point, turn on the

low level warning light, and if the liquid level goes above the
high level set point, turn on the high level warning light.

4. Convert the individual analog scaled data words to BCD and send

the data to the respective LED displays.