Module update time – Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 36

Advertising
background image

4–5

Preliminary Operating Considerations

Publication 1746Ć6.8 - April 1997

The module update time is defined as the time required for the
module to sample and convert the input signals of all enabled input
channels and provide the resulting data values to the SLC processor.
Module update time can be calculated by adding the the sum of all
enabled channel sample times (0.75 msec per channel).

The 1746-NI8 module sequentially samples the channels in a
continuous loop.

Channel 0 Disabled

Channel 1 Disabled

Channel 2 Disabled

Channel 3 Disabled

Sample

Channel 0

Sample

Channel 1

Sample

Channel 2

Sample

Channel 3

Enabled

Enabled

Enabled

Enabled

Channel 4 Disabled

Channel 5 Disabled

Channel 6 Disabled

Channel 7 Disabled

Sample

Channel 4

Sample

Channel 5

Sample

Channel 6

Sample

Channel 7

Enabled

Enabled

Enabled

Enabled

The following table shows the module update time. The module
update time is the same regardless of the filter frequency. The fastest
module update time occurs when only one channel is enabled. The
slowest module update time occurs when 8 channels are enabled.

Module Update Time

Number of Channels Enabled

Update Time

1

0.75 msec

2

1.50 msec

3

2.25 msec

4

3.00 msec

5

3.75 msec

6

4.50 msec

7

5.25 msec

8

6.00 msec

Module Update Time