Configure the Adapter for Direct Connection
through the RSLogix 5000 or Logix Designer
Application

Overview

In the following example, a ControlLogix controller communicates with I/O
modules through the adapter using a direct connection.

The adapter makes a direct connection to each of the modules referenced by the
data. The modules presented in this chapter use RSLogix 5000/Logix Designer
application, revision 20 or later.

Set Up the Hardware

In this example, a ControlLogix chassis contains the Logix5575 controller in slot
1 and a 1756-EN2TR bridge module in slot 3. The 1747-AENTR adapter is
mounted on an SLC chassis in slot 0, with a 1746-IO8 input module in slot 1, a
1746-IA4 module in slot 2, a 1746-BAS/B module in slot 3, and a power supply.

Topic

Page

Set Up the Hardware

27

Create the Example Application

28

Configure the I/O

29

Add the Local EtherNet/IP Bridge to the I/O Configuration

30

Add the Adapter to the I/O Configuration

31

Add I/O Modules to the I/O Configuration

33

Download the Program to the Controller

42

Custom Settings (Edit Adapter Configuration)

43

Custom Settings for your I/O Module

46

IMPORTANT

The steps and screenshots used in this chapter refer to the
RSLogix 5000 software, which has since been renamed to
Logix Designer application.

The configuration process in the Logix Designer application follows
the same steps as the configuration process in RSLogix 5000.

IMPORTANT

The 1747-AENTR device should always be installed in Slot 0. There
should only be one 1747-AENTR device installed within the same
rack or its connected rack extensions for multiple chassis support.