Rockwell Automation 1747-AENTR SLC 500 EtherNet/IP Adapter User Manual User Manual
Page 46
40
Rockwell Automation Publication 1747-UM076C-EN-E - January 2013
40 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application
7. Click Configuration tab.
The Chunk configuration determines the 1747-AENTR SLC backplane
scan. Set up the chunks as follows:
• Output Chunk 1
– Size = 8 (number of Output INTs to scan)
– File = Output File
– Offset = 0 (starting INT offset in Output File)
• Output Chunk 2
– Size = 64 (number of M0 INTs to scan)
– File = M0 File
– Offset = 0 (starting INT offset in M0 File)
• Output Chunk 3
– Size = 0
– File = <Don’t Care>
– Offset = 0
• Input Chunk 1
– Size = 8 (number of Input INTs to scan)
– File = Input File
– Offset = 0 (starting INT offset in Input File)
• Input Chunk 2
– Size = 64 (number of M1 INTs to scan)
– File = M1