46 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

To configure the ports:

7. Click OK.

Custom Settings for your
I/O Module

You can edit the default configuration of your 1746/1747 module through the
Module Properties dialog available in RSLogix 5000.

To Then

Use the default port speed and
duplex settings

Leave Auto-negotiate port speed and duplex checked.
This setting determines the actual speed and duplex setting.

Manually configure your port’s
speed and duplex settings

Follow these steps.
1. Clear the Auto-negotiate port speed and duplex checkbox.
2. From the Current Port Speed pull-down menu, choose a

port speed.

3. From the Current Duplex pull-down menu, choose the

appropriate Duplex value, that is, Half Duplex or Full
Duplex.

IMPORTANT

Consider the following when you configure the module’s port settings:

• If the module is connected to an unmanaged switch, leave

Auto-negotiate port speed and duplex checked or the module
will fail.

• If you are forcing the port speed and duplex with a managed

switch, the corresponding port of the managed switch must be
forced to the same settings or the module will fail.

IMPORTANT

To fully customize the settings of your I/O module, consult the User
Manual for your module. User Manuals and other reference publications
for 1746/1747 modules are available in the Rockwell Automation
Literature Library:

http://rockwellautomation.com/literature