42 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application

After adding the 1746-BAS/B module, the I/O Configuration tree should
appear as follows:

Download the Program to
the Controller

Follow this procedure to download the program you just saved to the
ControlLogix controller.

1. From the main menu, choose Communications>Who-Active.

The Who Active dialog opens.

2. Navigate to select the slot where the controller is located in the chassis.
3. Choose Set Project Path.
4. Choose Download.

The Download dialog opens with a reminder of the following.
• The controller is in Remote Run mode.