Rockwell Automation Publication 1747-UM076C-EN-E - January 2013
36 Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application
5. Enter 50 for requested packet interval (RPI) to set how often you exchange
data with the I/O adapter.
6. Click OK to save the configuration.
The module now appears under the I/O Configuration tree.
IMPORTANT
The default RPI of 20 ms is suitable for typical applications.
TIP
Rockwell Automation recommends that you check or enable the option
“Major Fault On Controller If Connection Fails While in Run Mode” on
both the 1747-AENTR device and supported 1746 I/O modules.