Rockwell Automation Publication 1747-UM076C-EN-E - January 2013

43

Configure the Adapter for Direct Connection through the RSLogix 5000 or Logix Designer Application 43

• The mode changes to Remote Program prior to download.

5. On the Download dialog, choose Download.

The RSLogix 5000/Studio 5000 software dialog opens.

Notice that the 1756-EN2TR Bridge is now online.

Custom Settings
(Edit Adapter Configuration)

You have now built the I/O Configuration tree in the RSLogix 5000 software.
You can edit the configuration of the 1747-AENTR adapter through the Module
Properties screen.

The RSLogix 5000 software automatically creates module-defined data types and
tags when a module is created. This section describes how to modify the default
configuration.

Data types symbolically name module configuration, input and output data. Tags
let you provide each a unique name, such as where the user-defined data type and
slot reside on the controller. This information is used to communicate data
between the controller and module.

Follow these steps to modify the default adapter configuration.