Event codes for dsi drives, Driveexplorer or driveexecutive software only) -7 – Rockwell Automation 1203-USB Converter User Manual

Page 55

Advertising
background image

Troubleshooting

4-7

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

Event Codes for DSI Drives

Event Codes for SCANport Drives

(DriveExplorer or DriveExecutive software only)

Code Event

Description

F0

No Event

No event present in the event queue.

F1

Adapter Reset

The converter was reset by the user.

F2

Slave Detected

A slave was detected to be present by the master.

F3

Slave Removed

A slave was detected to be removed by the master.

F4

Host Timeout

A timeout condition on Msg to Host.

F5

Slave Timeout

A timeout condition on Msg to Slave.

F6

Master Timeout

A timeout condition on Msg to Master.

F7

Serial Timeout

A timeout on Serial 232 side (with control enabled).

F8

Control Enabled

The converter has sent a ‘Soft Control Enable’ command to the drive.

F9

Control Disabled

The converter has sent a ‘Soft Control Disable’ command to the drive.

F10

EEPROM Sum Flt

Startup sequence detected corrupt EEPROM storage in the converter.

Events

Description

Adapter Reset

The converter was reset or power cycled.

Clear SP Fault

The SCANport drive issued this because a fault was cleared in it.

Clear SP Warning

The SCANport drive issued this because a warning was cleared.

Empty Queue

The queue does not contain any recorded events.

Message Timeout

The SCANport drive did not respond to a message request. Verify that cabling

is correct.

No SCANport Ping

The converter issued this because no SCANport pings were detected within a

2 second period. This event may be caused by a disconnected or broken

cable, a broken converter, or a malfunction in the SCANport drive.

Pin ID Change

The converter issued this because the SCANport Pin ID was changed. This

event is normal after a power cycle or reset.

SCANport Bus Off

The converter issued this because its SCANport CAN chip went bus off. This

event may be caused by loose or broken cables, or by noise.

SCANport Fault

The SCANport drive issued this because it was faulted. See its fault queue.

SCANport Reset

The SCANport drive issued this because it was reset.

SCANport Warning

The SCANport drive issued this because it had a warning.

SP Pin ID = 7

The converter issued this because its Pin ID has a value of 7. It should have a

value between 1 and 6. This event may be caused by a loose or broken cable.