Rockwell Automation 1203-USB Converter User Manual

Page 67

Advertising
background image

Use with DriveExplorer Software

C-3

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

Important: DriveExplorer software has its own drivers. If a driver has

been configured using RSLinx software for that same COM
port, it must be deleted with RSLinx software before
DriveExplorer is launched.

3. If not already running, launch DriveExplorer Lite software (or the full

version of DriveExplorer software).

4. From the Explore menu, choose Configure Communication.

5. Select the COM port noted in step 1 and a baud rate of ‘115200’.

6. Select either checksum, and accept the default time for the Comm

Timeout.

7. Click OK.

8. Choose Explore > Connect > Serial Point-to-Point.

A node eventually appears in the DriveExplorer window under Devices
in the treeview.

9. In the left pane, click the Parameter List for the 1203-USB converter or

connected drive to display its parameters in the right pane.

10. Double-click a parameter to edit it.