Use with DriveExecutive Software

D-11

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

Configuring the Converter for RTU Master Mode

1. From the pull-down menu in the Value column of the 1203-USB Linear

List dialog box for converter Parameter 01 - [Adapter Cfg], choose
‘3’ (RTU Master).

2. Remove power from the drive to which the 1203-USB converter is

connected, which temporarily ends communications.

3. Electrically connect all drives to create the RTU Master network.

See

Network Wiring on page 3-8

for details.

Configuring RSLinx for Serial Multi-Drop

The Configured Driver in RSLinx is slightly different when configuring for
a RS-485 multi-drop system as opposed to a point-to-point system (single
drive).

1. Open RSLinx software.

2. From the Communications menu, choose Configure Drivers.