Temperature rating – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

Chapter 1 Wire/Cable Types

Figure 1 - Wire Selection Flowchart

Temperature Rating

In general, follow these temperature ratings for installations:

In surrounding air temperature of 50 °C (122 °F), use 90 °C (194 °F) wire
(required for UL)

In surrounding air temperature of 40 °C (104 °F), use 75 °C (167 °F) wire
(required for UL)

Refer to the user manual of the drive for other restrictions.

XLPE

PVC

20 mil or > (1)

230V

400/460V

15 mil

> 15.2 m (50 ft)

< 15.2 m (50 ft)

575V

Selecting Wire to Withstand Reflected Wave Voltage for New and Existing Wire Installations in

Conduit or Cable Trays

Conductor

Environment

Conductor
Insulation

Insulation

Thickness

DRY

(per NEC Article 100)

WET

(per NEC Article 100)

XLPE (XHHW-2)

Insulation for

< 600V AC

System

No RWR or

Terminator

Required

OK for < 600V AC

System

No RWR or

Terminator Required

Reflected Wave

Reducer?

RWR or

Terminator

No RWR or

Terminator

RWR or

Terminator

No RWR or

Terminator

Reflected Wave

Reducer?

Cable

Length

Number of

Drives in Same

Conduit or Wire

Tray

15 mil PVC

in Not

Recommended.

Use XLPE

or > 20 mil

15 mil PVC

is Not

Recommended.

Use XLPE

or > 20 mil

Multiple Drives

in Single Conduit

or Wire Tray

Single Drive,

Single Conduit or

Wire Tray

See NEC Guidelines (Article 310

Adjustment Factors) for Maximum

Conductor Derating and Maximum

Wires in Conduit or Tray

(1) The minimum wire size for PVC cable with 20 mil or greater insulation is 10 gauge.

IMPORTANT

The temperature rating of the wire affects the required gauge. Verify that your
installation meets all applicable national, state, and local codes.