Chapter 3 Grounding

Effective Grounding Practices

This scheme replaces the conduit with shielded or armored cable that has a PVC
exterior jacket. This PVC jacket prevents accidental contact with building steel
and reduces the possibility that noise can enter the ground grid.

Optimal – Recommended Grounding Practices

The fully grounded scheme provides the best containment of common mode
noise. It uses PVC jacketed, shielded cable on both the input and the output to
the drive. This method also provides a contained noise path to the transformer to
keep the ground grid as clean as possible.

X0

R

S

T

U

V

W

PE

PE

A

B

C

PE

Input Transformer

AC Drive

Motor Frame

Motor

Connection to Drive Structure or

Optional Cabinet Via Grounding

Connector or Terminating Shield

at PE Terminal

Motor Frame

Ground

Connection to Ground Grid,

Girder, or Ground Rod

Connection to Cabinet Ground Bus

or Directly to Drive PE Terminal

Panel Ground Bus

Optional Enclosure

Building Ground Potential

Shielded or Armored

Cable with PVC Jacket

PVC

X0

R

S

T

U

V

W

PE

PE

A

B

C

PE

Input Transformer

Shielded or

Armored Cable

with PVC Jacket

Shielded or

Armored Cable

with PVC Jacket

AC Drive

Motor Frame

Motor

PVC

PVC

Motor Frame

Ground

Connection to Drive Structure or

Optional Cabinet Via Grounding

Connector or Terminating Shield

at PE Terminal

Panel Ground Bus

Optional Enclosure

Connection to Cabinet

Ground Bus or Directly

to Drive PE Terminal

Building Ground Potential

Connection to Drive

Structure or Optional

Cabinet Via Grounding

Connector or Terminating

Shield at PE Terminal

Connection to Ground Grid,

Girder or Ground Rod