1305 drives – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 127

Advertising
background image

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

127

Motor Cable Length Restrictions Tables Appendix A

1305 Drives

This section lists motor cable data for 1305 drives.

Table 56 - 1305 Drives, 480V, No External Devices at Motor – Meters (Feet)

Table 57 - 1305 Drive, 480V with Devices at Motor – Meters (Feet)

Drive Hp
(480V)

Motor Hp
(480V)

(480V) Using a Motor with Insulation V

P-P

Type A

Type B

1329R/L

Any Cable

Any Cable

Shielded Cable

Unshielded Cable

Maximum Carrier Frequency

4 kHz

4 kHz

2 kHz

2 kHz

High-line Derate Multiplier

0.85

0.85

0.55

0.55

5

5

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

3

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

2

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

1

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

0.5

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

3

3

9.1 (30)

30.5 (100)

91.4 (300)

121.9 (400)

2

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

1

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

0.5

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

2

2

9.1 (30)

30.5 (100)

76.2 (250)

121.9 (400)

1

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

0.5

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

1

1

9.1 (30)

30.5 (100)

68.6 (225)

121.9 (400)

0.5

9.1 (30)

30.5 (100)

121.9 (400)

121.9 (400)

0.5

0.5

9.1 (30)

30.5 (100)

45.7 (150)

106.7 (350)

Drive Hp
(460V)

Motor Hp
(460V)

Reactor at the Drive

(1)

(1) IMPORTANT: A 3% reactor reduces motor stress but can cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100V or higher. Reactors are

not recommended for lightly loaded applications because over voltage trips can result at low output frequencies.

With 1204-TFB2 Terminator

With 1204-TFA1 Terminator

Using a Motor with Insulation V

P-P

Using a Motor with Insulation VP-P

(NR = not recommended)

Using a Motor with Insulation VP-P

(NR = not recommended)

Type A

Type B or 1329R/L

Type A or Type B

Type A

Type B

Any Cable

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Shielded

Unshielded

Maximum Carrier Frequency

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

2 kHz

High-line Derating Multiplier

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

0.85

5

5

15.2 (50)

182.9 (600)

182.9 (600)

NR

NR

91.4 (300)

61.0 (200)

91.4 (300)

121.9 (400)

3

15.2 (50)

182.9 (600)

182.9 (600)

91.4 (300)

121.9 (400)

99.1 (325)

61.0 (200)

152.4 (500)

121.9 (400)

2

15.2 (50)

182.9 (600)

182.9 (600)

121.9 (400)

182.9 (600)

99.1 (325)

61.0 (200)

182.9 (600)

121.9 (400)

1

15.2 (50)

182.9 (600)

182.9 (600)

121.9 (400)

182.9 (600)

99.1 (325)

61.0 (200)

182.9 (600)

121.9 (400)

0.5

15.2 (50)

182.9 (600)

182.9 (600)

182.9 (600)

182.9 (600)

99.1 (325)

61.0 (200)

182.9 (600)

121.9 (400)

3

3

15.2 (50)

91.4 (300)

182.9 (600)

NR

NR

91.4 (300)

61.0 (200)

91.4 (300)

121.9 (400)

2

15.2 (50)

182.9 (600)

182.9 (600)

91.4 (300)

121.9 (400)

99.1 (325)

61.0 (200)

152.4 (500)

121.9 (400)

1

15.2 (50)

182.9 (600)

182.9 (600)

91.4 (300)

182.9 (600)

99.1 (325)

61.0 (200)

182.9 (600)

121.9 (400)

0.5

15.2 (50)

182.9 (600)

182.9 (600)

121.9 (400)

182.9 (600)

99.1 (325)

61.0 (200)

182.9 (600)

121.9 (400)

2

2

15.2 (50)

76.2 (250)

167.6 (550)

NR

NR

91.4 (300)

61.0 (200)

91.4 (300)

121.9 (400)

1

15.2 (50)

182.9 (600)

182.9 (600)

61.0 (200)

61.0 (200)

99.1 (325)

61.0 (200)

121.9 (400)

121.9 (400)

0.5

15.2 (50)

182.9 (600)

182.9 (600)

91.4 (300)

121.9 (400)

99.1 (325)

61.0 (200)

152.4 (500)

121.9 (400)

1

1

15.2 (50)

68.6 (225)

152.4 (500)

NR

NR

45.7 (150)

61.0 (200)

45.7 (150)

76.2 (250)

0.5

15.2 (50)

182.9 (600)

182.9 (600)

NR

NR

76.2 (250)

61.0 (200)

76.2 (250)

121.9 (400)

0.5

0.5

15.2 (50)

45.7 (150)

106.7 (350)

NR

NR

NR

NR

NR

NR

Advertising