Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 87
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
87
Motor Cable Length Restrictions Tables Appendix A
Table 20 - PowerFlex 40 Drives, 600V Shielded/Unshielded Cable – Meters (Feet)
Rating
No Solution
Reactor Only
Reactor and
Damping Resistor
or 1321-RWR
Reactor/RWR
(see
)
Resistor
Available Options
Hp
kHz
1488V
1850V
1488V
1600V
1488V
1600V
Cat. No.
Ohms
Watts
TF
A1
TF
B
2
RW
R2
RW
C
1
2/4
42.7
(140)
121.9
(400)
121.9
(400)
121.9
(400)
121.9
(400)
121.9
(400)
●
●
●
2
2/4
42.7
(140)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
152.4
(500)
●
●
●
3
2/4
42.7
(140)
152.4
(500)
152.4
(500)
152.4
(500)
182.9
(600)
182.9
(600)
●
●
●
5
2/4
42.7
(140)
152.4
(500)
152.4
(500)
243.8
(800)
243.8
(800)
243.8
(800)
1321-RWR8-DP
●
●
●
●
7.5
2/4
42.7
(140)
182.9
(600)
152.4
(500)
304.8
(1000)
304.8
(1000)
304.8
(1000)
1321-RWR12-DP
●
●
10
2/4
42.7
(140)
182.9
(600)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR18-DP
●
●
15
2/4
42.7
(140)
182.9
(600)
152.4
(500)
365.8
(1200)
365.8
(1200)
365.8
(1200)
1321-RWR25-DP
●