Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 31
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
31
Power Distribution Chapter 2
Table 5 - AC Line Impedance Recommendations for Bulletin 1305 Drives
Table 6 - AC Line Impedance Recommendations for PowerFlex 4 Drives
Bulletin
Number
Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts
kW (Hp)
Max Supply
kVA
(2)
(2) Maximum suggested KVA supply without consideration for additional inductance.
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
1305
-AA02A
240
0.37(0.5)
15
3R4-A
3
4
-AA03A
240
0.55 (0.75) 20
3R4-A
4
4
-AA04A
240
0.75 (1)
30
3R8-A
1.5
8
-AA08A
240
1.5 (2)
50
3R8-A
1.5
8
-AA12A
240
2.2 (3)
75
3R18-A
0.8
18
-BA01A
480
0.37 (0.5)
15
3R2-B
20
2
-BA02A
480
0.55 (0.75) 20
3R2-B
20
2
-BA03A
480
0.75 (1)
30
3R4-B
6.5
4
-BA04A
480
1.5 (2)
50
3R4-B
6.5
4
-BA06A
480
2.2 (3)
75
3R8-B
3
8
-BA09A
480
3.7 (5)
100
3R18-B
1.5
18
Drive
Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts
kW (Hp)
Max Supply
kVA
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
4
22AB1P5
240
0.2 (0.25)
15
3R2-A
12
2
22AB2P3
240
0.4 (0.5)
25
3R4-B
6.5
4
22AB4P5
240
0.75 (1.0)
50
3R8-B
3
8
22AB8P0
240
1.5 (2.0)
100
3R8-A
1.5
8
22AB012
240
2.2 (3.0)
125
3R12-A
1.25
12
22AB017
240
3.7 (5.0)
150
3R18-A
0.8
18
22AD1P4
480
0.4 (0.5)
15
3R2-B
20
2
22AD2P3
480
0.75 (1.0)
30
3R4-C
9
4
22AD4P0
480
1.5 (2.0)
50
3R4-B
6.5
4
22AD6P0
480
2.2 (3.0)
75
3R8-C
5
8
22AD8P7
480
3.7 (5.0)
100
3R8-B
3
8