Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 31

Advertising
background image

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

31

Power Distribution Chapter 2

Table 5 - AC Line Impedance Recommendations for Bulletin 1305 Drives

Table 6 - AC Line Impedance Recommendations for PowerFlex 4 Drives

Bulletin
Number

Drive Catalog
Number

(1)

(1) Shaded rows identify drive ratings without built-in inductors.

Volts

kW (Hp)

Max Supply
kVA

(2)

(2) Maximum suggested KVA supply without consideration for additional inductance.

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

1305

-AA02A

240

0.37(0.5)

15

3R4-A

3

4

-AA03A

240

0.55 (0.75) 20

3R4-A

4

4

-AA04A

240

0.75 (1)

30

3R8-A

1.5

8

-AA08A

240

1.5 (2)

50

3R8-A

1.5

8

-AA12A

240

2.2 (3)

75

3R18-A

0.8

18

-BA01A

480

0.37 (0.5)

15

3R2-B

20

2

-BA02A

480

0.55 (0.75) 20

3R2-B

20

2

-BA03A

480

0.75 (1)

30

3R4-B

6.5

4

-BA04A

480

1.5 (2)

50

3R4-B

6.5

4

-BA06A

480

2.2 (3)

75

3R8-B

3

8

-BA09A

480

3.7 (5)

100

3R18-B

1.5

18

Drive

Drive Catalog
Number

(1)

(1) Shaded rows identify drive ratings without built-in inductors.

Volts

kW (Hp)

Max Supply
kVA

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

PowerFlex

4

22AB1P5

240

0.2 (0.25)

15

3R2-A

12

2

22AB2P3

240

0.4 (0.5)

25

3R4-B

6.5

4

22AB4P5

240

0.75 (1.0)

50

3R8-B

3

8

22AB8P0

240

1.5 (2.0)

100

3R8-A

1.5

8

22AB012

240

2.2 (3.0)

125

3R12-A

1.25

12

22AB017

240

3.7 (5.0)

150

3R18-A

0.8

18

22AD1P4

480

0.4 (0.5)

15

3R2-B

20

2

22AD2P3

480

0.75 (1.0)

30

3R4-C

9

4

22AD4P0

480

1.5 (2.0)

50

3R4-B

6.5

4

22AD6P0

480

2.2 (3.0)

75

3R8-C

5

8

22AD8P7

480

3.7 (5.0)

100

3R8-B

3

8