This table contains examples that illustrate methods for mitigating transient
interference.

Examples of Transient Interference Mitigation

Example 1
A contact output controls a DC control
relay.
The relay coil requires a suppressor
(blocking diode) because it is an inductive
device controlled by a dry contact.

Example 2
A DC output controls a motor starter,
contacts on the starter control a motor.
The contacts require RC networks or
varistors.
The motor requires suppressors because it
is an inductive device.
An inductive device controlled by a solid
state switching device (like the starter coil
in this example) typically does not require
a suppressor.

Example 3
An AC output controls an interposing relay,
but the circuit can be opened by dry
contacts. Relay contacts control a solenoid
coil.
The contacts require RC networks or
varistors.
The relay coil requires a suppressor because
it is an inductive device controlled by dry
contacts.
The solenoid coil also requires a suppressor
because it is an inductive device controlled
by dry contacts.

Example 4
A contact output controls a pilot light with
a built in step-down transformer.
The pilot light requires a suppressor
because its transformer is an inductive
device controlled by a dry contact.

Example 5
A contact output controls a relay that
controls a brake solenoid.
The contacts require RC networks or
varistors.
Both the relay and the brake solenoid
require suppressors because they are both
inductive devices controlled by dry
contacts.

1CR

V DC

Digital Contact Output

L1

L2

1MS

L1

1MS

1M

L2

1MS

1MS

L1

Digital DC Output

Solid-state

Switch

Suppressor

Suppressor

Su

ppr

es

so

r

2L

1L

1CR

1CR

1S

Solid-state

Switch

Suppressor

Suppressor

Digital AC Output

L1

L2

Digital Contact Output

Suppressor

Pilot Light with Built-in

Step-down Transformer

1CR

115V AC

480V AC

RC

1

RC

1

Digital Contact Output

Suppressor

Suppressor

Brake Solenoid

Advertising