Appendix A Motor Cable Length Restrictions Tables

Table 29 - PowerFlex 700 (standard/vector) Drives, 690V Shielded/Unshielded Cable – Meters (Feet)

PowerFlex 700H

This section lists motor cable length restrictions, reactors, and available options
for PowerFlex 700H drives.

Table 30 - PowerFlex 700H Drives, 400V Shielded/Unshielded Cable – Meters (Feet)

Drive

No Solution

Reactor Only

Reactor and Damping Resistor Reactor

Resistor

Available Options

Frame kW

kHz

1850V

2000V

1850V

2000V

1850V

2000V

Cat. No.

Ohms Watts

TF

A1

TF

B

2

RW

R2

RW

C

4

45

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R80-C

50

345

4

24.4 (80)

76.2 (250)

36.6 (120)

121.9 (400)

213.4 (700)

274.3 (900)

1321-3R80-C

50

690

55

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R80-C

50

345

4

24.4 (80)

76.2 (250)

36.6 (120)

106.7 (350)

213.4 (700)

274.3 (900)

1321-3R80-C

50

690

5

75

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R100-C

50

345

4

30.5 (100)

76.2 (250)

36.6 (120)

106.7 (350)

213.4 (700)

274.3 (900)

1321-3R100-C

50

690

90

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R130-C

50

375

4

30.5 (100)

76.2 (250)

36.6 (120)

106.7 (350)

182.9 (600)

274.3 (900)

1321-3R130-C

50

750

6

110

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R160-C

50

375

4

30.5 (100)

76.2 (250)

36.6 (120)

99.1 (325)

152.4 (500)

274.3 (900)

1321-3R160-C

50

750

132

2

30.5 (100)

106.7 (350)

91.4 (300)

152.4 (500)

365.8 (1200)

365.8 (1200)

1321-3R200-C

50

375

4

30.5 (100)

76.2 (250)

36.6 (120)

83.8 (275)

152.4 (500)

274.3 (900)

1321-3R200-C

50

750

Drive

No Solution

Reactor Only

Reactor and Damping Resistor
or 1321-RWR

Reactor/RWR

(see

page 129

)

Resistor

Available Options

Frame kW

kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No.

Ohms

Watts

TF

A1

TF

B2

RW

R2

RW

C

9

132

2

24.4
(80)

48.8
(160)

76.2
(250)

137.2
(450)

24.4
(80)

48.8
(160)

365.8
(1200)

365.8
(1200)

121.9
(400)

274.3
(900)

365.8
(1200)

365.8
(1200)

1321-RWR320-DP

160

2

24.4
(80)

48.8
(160)

76.2
(250)

137.2
(450)

24.4
(80)

48.8
(160)

365.8
(1200)

365.8
(1200)

121.9
(400)

274.3
(900)

365.8
(1200)

365.8
(1200)

1321-RWR320-DP

10

200

2

24.4
(80)

48.8
(160)

76.2
(250)

121.9
(400)

24.4
(80)

48.8
(160)

365.8
(1200)

365.8
(1200)

121.9
(400)

274.3
(900)

365.8
(1200)

365.8
(1200)

1321-3R500-B

20

495

(3)

(3) Resistor specification is based on two cables per phase.

250

2

24.4
(80)

48.8
(160)

61.0
(200)

121.9
(400)

24.4
(80)

48.8
(160)

365.8
(1200)

365.8
(1200)

121.9
(400)

274.3
(900)

365.8
(1200)

365.8
(1200)

1321-3R500-B

20

495

(3)

11

315

2

18.3
(60)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

365.8
(1200)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

1321-3R600-B

20

495

(3)

355

2

18.3
(60)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

304.8
(1000)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

1321-3R750-B

20

495

(3)

400

2

18.3
(60)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

274.3
(900)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

1321-3R750-B

20

735

(4)

(4) Resistor specification is based on three cables per phase.

12

(1)

(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.

450

2

18.3
(60)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

243.8
(800)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

2 x
1321-3RB400-B

40

375

(4)

500

2

12.2
(40)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

243.8
(800)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

2 x

1321-3R500-B

40

375

(4)

560

2

12.2
(40)

42.7
(140)

61.0
(200)

121.9
(400)

18.3
(60)

42.7
(140)

243.8
(800)

365.8
(1200)

121.9
(400)

243.8
(800)

365.8
(1200)

365.8
(1200)

2 x

1321-3R500-B

20

525

(5)

(5) Resistor specification is based on four cables per phase.

13

630

(2)

(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.

2

12.2
(40)

61.0
(200)

99.1
(325)

167.6
(550)

36.6
(120)

61.0
(200)

304.8
(1000)

365.8
(1200)

198.1
(650)

274.3
(900)

365.8
(1200)

365.8
(1200)

2 x

1321-3R600-B

20

525

(5)

710

(2)

2

12.2
(40)

61.0
(200)

99.1
(325)

167.6
(550)

36.6
(120)

61.0
(200)

304.8
(1000)

365.8
(1200)

198.1
(650)

274.3
(900)

365.8
(1200)

365.8
(1200)

2 x

1321-3R750-B

20

525

(5)

800

(2)

2

12.2
(40)

61.0
(200)

99.1
(325)

167.6
(550)

36.6
(120)

61.0
(200)

304.8
(1000)

365.8
(1200)

198.1
(650)

274.3
(900)

365.8
(1200)

365.8
(1200)

2 x

1321-3R750-B

20

525

(5)