Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 32
32
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
Table 7 - AC Line Impedance Recommendations for PowerFlex 40 Drives
Drive
Drive Catalog
Number
(1)
(1) Shaded rows identify drive ratings without built-in inductors.
Volts
kW (Hp)
Max Supply
kVA
(2)
(2) Maximum suggested KVA supply without consideration for additional inductance.
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
40
22BB2P3
240
0.4 (0.5)
25
3R4-B
6.5
4
22BB5P0
240
0.75 (1.0)
50
3R8-B
3
8
22BB8P0
240
1.5 (2.0)
50
3R8-A
1.5
8
22BB012
240
2.2 (3.0)
50
3R12-A
1.25
12
22BB017
240
3.7 (5.0)
50
3R18-A
0.8
18
22BB024
240
5.5 (7.5)
100
3R25-A
0.5
25
22BB033
240
7.5 (10.0)
150
3R35-A
0.4
35
22BD1P4
480
0.4 (0.5)
15
3R2-B
20
2
22BD2P3
480
0.75 (1.0)
30
3R4-C
9
4
22BD4P0
480
1.5 (2.0)
50
3R4-B
6.5
4
22BD6P0
480
2.2 (3.0)
75
3R8-C
5
8
22BD010
480
3.7 (5.0)
100
3R8-B
3
8
22BD012
480
5.5 (7.5)
120
3R12-B
2.5
12
22BD017
480
7.5 (10.0)
150
3R18-B
1.5
18
22BD024
480
11.0 (15.0) 200
3R25-B
1.2
25
22BE1P7
600
0.75 (1.0)
20
3R2-B
20
2
22BE3P0
600
1.5 (2.0)
30
3R4-B
6.5
4
22BE4P2
600
2.2 (3.0)
50
3R4-B
6.5
4
22BE6P6
600
3.7 (5.0)
75
3R8-C
5
8
22BE9P9
600
5.5 (7.5)
120
3R12-B
2.5
12
22BE012
600
7.5 (10.0)
150
3R12-B
2.5
12
22BE019
600
11.0 (15.0) 200
3R18-B
1.5
18