Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

Chapter 2 Power Distribution

1336 PLUS,
PLUS II
IMPACT
FORCE

B025

480

18.5 (25)

550

3R35-B

0.8

35

B030

480

22 (30)

600

3R45-B

0.7

45

B040

480

30 (40)

750

3R55-B

0.5

55

B050

480

37 (50)

800

3R80-B

0.4

80

B060

480

45 (60)

900

3R80-B

0.4

80

B075

480

56 (75)

1000

3R100-B

0.3

100

B100

480

75 (100)

1000

3R130-B

0.2

130

B125

480

93 (125)

1400

3R160-B

0.15

160

B150

480

112 (150)

1500

3R200-B

0.11

N200

B200

480

149 (200)

2000

3RB250-B

0.09

250

B250

480

187 (250)

2500

3RB320-B

0.075

320

B300

480

224 (300)

3000

3RB400-B

0.06

400

B350

480

261 (350)

3500

3R500-B

0.05

500

B400

480

298 (400)

4000

3R500-B

0.05

500

B450

480

336 (450)

4500

3R600-B

0.04

600

B500

480

373 (500)

5000

3R600-B

0.04

600

B600

480

448 (600)

5000

3R750-B

0.029

750

B700

480

(700)

5000

3R850-B

0.027

850

B800

480

(800)

5000

3R1000-B

0.022

1000

BP/BPR250

480

187 (250)

N/A

N/A

N/A

N/A

BP/BPR300

480

224 (300)

N/A

N/A

N/A

N/A

BP/BPR350

480

261 (350)

N/A

N/A

N/A

N/A

BP/BPR400

480

298 (400)

N/A

N/A

N/A

N/A

BP/BPR450

480

336 (450)

N/A

N/A

N/A

N/A

BX040

480

30 (40)

N/A

N/A

N/A

N/A

BX060

480

45 (60)

N/A

N/A

N/A

N/A

BX150

480

112 (150)

N/A

N/A

N/A

N/A

BX250

480

187 (250)

N/A

N/A

N/A

N/A

CWF10

600

0.75 (1)

25

3R4-C

9

4

CWF20

600

1.5 (2)

50

3R4-C

9

4

CWF30

600

2.2 (3)

75

3R8-C

5

8

CWF50

600

3.7 (5)

100

3R8-B

3

8

CWF75

600

5.5 (7.5)

200

3R8-B

3

8

CWF100

600

7.5 (10)

200

3R12-B

2.5

12

CWF150

600

11 (15)

300

3R18-B

1.5

18

CWF200

600

15 (20)

350

3R25-B

1.2

25

C015

600

11 (15)

300

3R18-B

1.5

18

C020

600

15 (20)

350

3R25-B

1.2

25

C025

600

18.5 (25)

500

3R25-B

1.2

25

C030

600

22 (30)

600

3R35-B

0.8

35

C040

600

30 (40)

700

3R45-B

0.7

45

C050

600

37 (50)

850

3R55-B

0.5

55

C060

600

45 (60)

900

3R80-B

0.4

80

C075

600

56 (75)

950

3R80-B

0.4

80

C100

600

75 (100)

1200

3R100-B

0.3

100

C125

600

93 (125)

1400

3R130-B

0.2

130

C150

600

112 (150)

1500

3R160-B

0.15

160

C200

600

149 (200)

2200

3R200-B

0.11

200

continued

Table 13 - AC Line Impedance Recommendations for Bulletin 1336 Drives (Continued)

Drive

Drive Catalog
Number

(1)

Volts

kW (Hp)

Max Supply
kVA

(2)(3)

3% Line Reactor
Open Style, 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

(4)