Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 42
42
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
1336 PLUS,
PLUS II
IMPACT
FORCE
B025
480
18.5 (25)
550
3R35-B
0.8
35
B030
480
22 (30)
600
3R45-B
0.7
45
B040
480
30 (40)
750
3R55-B
0.5
55
B050
480
37 (50)
800
3R80-B
0.4
80
B060
480
45 (60)
900
3R80-B
0.4
80
B075
480
56 (75)
1000
3R100-B
0.3
100
B100
480
75 (100)
1000
3R130-B
0.2
130
B125
480
93 (125)
1400
3R160-B
0.15
160
B150
480
112 (150)
1500
3R200-B
0.11
N200
B200
480
149 (200)
2000
3RB250-B
0.09
250
B250
480
187 (250)
2500
3RB320-B
0.075
320
B300
480
224 (300)
3000
3RB400-B
0.06
400
B350
480
261 (350)
3500
3R500-B
0.05
500
B400
480
298 (400)
4000
3R500-B
0.05
500
B450
480
336 (450)
4500
3R600-B
0.04
600
B500
480
373 (500)
5000
3R600-B
0.04
600
B600
480
448 (600)
5000
3R750-B
0.029
750
B700
480
(700)
5000
3R850-B
0.027
850
B800
480
(800)
5000
3R1000-B
0.022
1000
BP/BPR250
480
187 (250)
N/A
N/A
N/A
N/A
BP/BPR300
480
224 (300)
N/A
N/A
N/A
N/A
BP/BPR350
480
261 (350)
N/A
N/A
N/A
N/A
BP/BPR400
480
298 (400)
N/A
N/A
N/A
N/A
BP/BPR450
480
336 (450)
N/A
N/A
N/A
N/A
BX040
480
30 (40)
N/A
N/A
N/A
N/A
BX060
480
45 (60)
N/A
N/A
N/A
N/A
BX150
480
112 (150)
N/A
N/A
N/A
N/A
BX250
480
187 (250)
N/A
N/A
N/A
N/A
CWF10
600
0.75 (1)
25
3R4-C
9
4
CWF20
600
1.5 (2)
50
3R4-C
9
4
CWF30
600
2.2 (3)
75
3R8-C
5
8
CWF50
600
3.7 (5)
100
3R8-B
3
8
CWF75
600
5.5 (7.5)
200
3R8-B
3
8
CWF100
600
7.5 (10)
200
3R12-B
2.5
12
CWF150
600
11 (15)
300
3R18-B
1.5
18
CWF200
600
15 (20)
350
3R25-B
1.2
25
C015
600
11 (15)
300
3R18-B
1.5
18
C020
600
15 (20)
350
3R25-B
1.2
25
C025
600
18.5 (25)
500
3R25-B
1.2
25
C030
600
22 (30)
600
3R35-B
0.8
35
C040
600
30 (40)
700
3R45-B
0.7
45
C050
600
37 (50)
850
3R55-B
0.5
55
C060
600
45 (60)
900
3R80-B
0.4
80
C075
600
56 (75)
950
3R80-B
0.4
80
C100
600
75 (100)
1200
3R100-B
0.3
100
C125
600
93 (125)
1400
3R130-B
0.2
130
C150
600
112 (150)
1500
3R160-B
0.15
160
C200
600
149 (200)
2200
3R200-B
0.11
200
continued
Table 13 - AC Line Impedance Recommendations for Bulletin 1336 Drives (Continued)
Drive
Drive Catalog
Number
(1)
Volts
kW (Hp)
Max Supply
kVA
(2)(3)
3% Line Reactor
Open Style, 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(4)