Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 99

Advertising
background image

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

99

Motor Cable Length Restrictions Tables Appendix A

Table 31 - PowerFlex 700H Drives, 480V Shielded/Unshielded Cable – Meters (Feet)

Drive

No Solution

Reactor Only

Reactor and Damping Resistor
or 1321-RWR

Reactor/RWR

(see

page 129

)

Resistor

Available Options

Frame Hp

kHz 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V 1000V 1200V 1488V 1600V Cat. No.

Ohms

Watts

TF

A1

TF

B

2

RW

R2

RW

C

9

200

2

12.2
(40)

24.4
(80)

42.7
(140)

76.2
(250)

12.2
(40)

24.4
(80)

106.7
(350)

152.4
(500)

61.0
(200)

167.6
(550)

304.8
(1000)

365.8
(1200)

1321-RWR320-DP

250

2

12.2
(40)

24.4
(80)

42.7
(140)

76.2
(250)

12.2
(40)

24.4
(80)

91.4
(300)

121.9
(400)

61.0
(200)

152.4
(500)

304.8
(1000)

365.8
(1200)

1321-RWR320-DP

10

300

2

12.2
(40)

24.4
(80)

42.7
(140)

76.2
(250)

12.2
(40)

24.4
(80)

76.2
(250)

91.4
(300)

61.0
(200)

121.9
(400)

304.8
(1000)

365.8
(1200)

1321-3RB400-B

20

495

(3)

(3) Resistor specification is based on two cables per phase.

350

2

12.2
(40)

24.4
(80)

42.7
(140)

76.2
(250)

12.2
(40)

24.4
(80)

76.2
(250)

91.4
(300)

61.0
(200)

121.9
(400)

304.8
(1000)

365.8
(1200)

1321-3R500-B

20

495

(3)

450

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

61.0
(200)

91.4
(300)

61.0
(200)

121.9
(400)

274.3
(900)

365.8
(1200)

1321-3R500-B

20

495

(3)

11

500

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

61.0
(200)

91.4
(300)

61.0
(200)

121.9
(400)

243.8
(800)

365.8
(1200)

1321-3R750-B

20

495

(3)

600

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

45.7
(150)

91.4
(300)

45.7
(150)

121.9
(400)

243.8
(800)

365.8
(1200)

1321-3R750-B

20

735

(4)

(4) Resistor specification is based on three cables per phase.

12

(1)

(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.

700

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

45.7
(150)

91.4
(300)

45.7
(150)

106.7
(350)

243.8
(800)

365.8
(1200)

2 x

1321-3RB400-B

40

375

(4)

800

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

45.7
(150)

91.4
(300)

45.7
(150)

106.7
(350)

243.8
(800)

365.8
(1200)

2 x

1321-3R500-B

40

375

(4)

900

2

12.2
(40)

24.4
(80)

36.6
(120)

61.0
(200)

12.2
(40)

24.4
(80)

45.7
(150)

91.4
(300)

45.7
(150)

106.7
(350)

243.8
(800)

365.8
(1200)

2 x

1321-3R500-B

20

525

(5)

(5) Resistor specification is based on four cables per phase.

13

1000

(2)

(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.

2

12.2
(40)

30.5
(100)

61.0
(200)

121.9
(400)

12.2
(40)

45.7
(150)

61.0
(200)

121.9
(400)

45.7
(150)

152.4
(500)

304.8
(1000)

365.8
(1200)

2 x

1321-3R600-B

20

525

(5)

1200

(2)

2

12.2
(40)

30.5
(100)

61.0
(200)

121.9
(400)

12.2
(40)

45.7
(150)

61.0
(200)

121.9
(400)

45.7
(150)

152.4
(500)

304.8
(1000)

365.8
(1200)

2 x

1321-3R750-B

20

525

(5)

1250

(2)

2

12.2
(40)

30.5
(100)

61.0
(200)

121.9
(400)

12.2
(40)

45.7
(150)

61.0
(200)

121.9
(400)

45.7
(150)

152.4
(500)

304.8
(1000)

365.8
(1200)

2 x

1321-3R750-B

20

525

(5)

Advertising