Chapter 2 Power Distribution

These recommendations are advisory and do not address all situations. Site
specific conditions must be considered to assure a quality installation.

Table 4 - AC Line Impedance Recommendations for Bulletin 160 Drives

EXAMPLE

The drive is rated 1 Hp, 480V, 2.7A input.

The supply transformer is rated 50,000 VA (50 kVA), 5% impedance.

Note that the percent (%) impedance has to be in per unit (5% becomes 0.05)
for the formula.

0.22% is less than 0.5%. Therefore, this transformer is too big for the drive.
Consider adding a line reactor.

IMPORTANT

Grouping multiple drives on one reactor is acceptable; however, the reactor
percent impedance must be large enough when evaluated for each drive
separately, not evaluated for all loads connected at once.

Bulletin
Number

Drive Catalog
Number

(1)

(1) Shaded rows identify drive ratings without built-in inductors.

Volts

kW (Hp)

Max Supply
kVA

(2)

(2) Maximum suggested KVA supply without consideration for additional inductance.

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

160

-AA02

240

0.37(0.5)

15

3R4-B

6.5

4

-AA03

240

0.55 (0.75) 20

3R4-A

3

4

-AA04

240

0.75 (1)

30

3R4-A

3

4

-AA08

240

1.5 (2)

50

3R8-A

1.5

8

-AA12

240

2.2 (3)

75

3R12-A

1.25

12

-AA18

240

3.7 (5)

100

3R18-A

0.8

18

-BA01

480

0.37(0.5)

15

3R2-B

20

2

-BA02

480

0.55 (0.75) 20

3R2-A

12

2

-BA03

480

0.75 (1)

30

3R2-A

12

2

-BA04

480

1.5 (2)

50

3R4-B

6.5

4

-BA06

480

2.2 (3)

75

3R8-B

3

8

-BA10

480

3.7 (5)

100

3R18-B

1.5

18

Z

drive

=

V

line-line

3 * I

input-rating

480V

3 * 2.7

=

= 102.6 Ohms

Z

xfmr

=

(V

line-line

)

2

VA

480

2

50,000

* % Impedance =

* 0.05 = 0.2304 Ohms

Z

xfmr

Z

drive

0.2304

102.6

= 0.00224 = 0.22%

=