Hardware – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual

Page 59

Advertising
background image

Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

59

Best Practices Chapter 4

Hardware

You can mount the drive and/or mounting panel with either bolts or welded
studs.

Figure 21 - Stud Mounting of Ground Bus or Chassis to Back Panel

Figure 22 - Bolt Mounting of Ground Bus or Chassis to Back Panel

If the drive chassis does not lay flat before the nuts/bolts are tightened, use
additional washers as shims so that the chassis does not bend when you tighten
the nuts.

Back Panel

Welded Stud

Paint-free Area

Nut

Flat Washer

Mounting Bracket or

Ground Bus

Star Washer

If the mounting bracket is coated with a non-conductive

material (anodized, painted, and so on), scrape the material

off around the mounting hole.

Flat Washer

Back Panel

Bolt

Paint-free Area

Nut

Flat Washer

Mounting Bracket or
Ground Bus

Star Washer

Nut

Flat Washer

Star Washer

Star Washer

If the mounting bracket is coated with a non-conductive

material (anodized, painted, or other), scrape the material off

around the mounting hole.

Advertising