Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 36
36
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Chapter 2 Power Distribution
PowerFlex
70
20AE031
600
22 (30)
1000
3R35-B
0.8
35
20AE042
600
30 (40)
1000
3R45-B
0.7
45
20AE051
600
37 (50)
1000
3R55-B
0.5
55
(1) Shaded rows identify drive ratings without built-in inductors.
(2) Maximum suggested KVA supply without consideration for additional inductance.
(3) N/A = not available at time of printing.
Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives
Drive
Drive Catalog
Number
Volts
kW (Hp)
Max Supply
KVA
(1)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
PowerFlex
700/700S
For
PowerFlex
700S,
replace 20B
with 20D.
20BB2P2
240
0.37 (0.5)
100
3R2-D
6
2
20BB4P2
240
0.75 (1)
125
3R4-A
3
4
20BB6P8
240
1.5 (2)
200
3R8-A
1.5
8
20BB9P6
240
2.2 (3)
300
3R12-A
1.25
12
20BB015
240
3.7 (5)
400
3R18-A
0.8
18
20BB022
240
5.5 (7.5)
500
3R25-A
0.5
25
20BB028
240
7.5 (10)
750
3R35-A
0.4
35
20BB042
240
11 (15)
1000
3R45-A
0.3
45
20BB052
240
15 (20)
1000
3R80-A
0.2
80
20BB070
240
18.5 (25)
1000
3R80-A
0.2
80
20BB080
240
22 (30)
1000
3R100-A
0.15
100
20BB104
240
30 (40)
1000
3R130-A
0.1
130
20BB130
240
37 (50)
1000
3R130-A
0.1
130
20BB154
240
45 (60)
1000
3R160-A
0.075
160
20BB192
240
55 (75)
1000
3R200-A
0.055
200
20BB260
240
75 (100)
1000
3R320-A
0.04
320
20BC1P3
400
0.37 (5)
250
3R2-B
20
2
20BC2P1
400
0.75 (1)
250
3R2-B
20
2
20BC3P5
400
1.5(2)
500
3R4-B
6.5
4
20BC5P0
400
2.2 (3)
500
3R4-B
6.5
4
20BC8P7
400
4 (5)
500
3R8-B
3
8
20BC011
400
5.5 (7.5)
750
3R12-B
2.5
12
20BC015
400
7.5 (10)
1000
3R18-B
1.5
18
20BC022
400
11 (15)
1000
3R25-B
1.2
25
20BC030
400
15 (20)
1000
3R35-B
0.8
35
20BC037
400
18.5(25)
1000
3R45-B
0.7
45
20BC043
400
22 (30)
1000
3R45-B
0.7
45
20BC056
400
30 (40)
1000
3R55-B
0.5
55
20BC072
400
37 (50)
1000
3R80-B
0.4
80
20BC085
400
45 (60)
1000
3R130-B
0.2
130
20BC105
400
55 (75)
1000
3R130-B
0.2
130
20BC125
400
55 (75)
1000
3R130-B
0.2
130
20BC140
400
75 (100)
1000
3R160-B
0.15
160
20BC170
400
90 (125)
1500
3R200-B
0.11
200
20BC205
400
110 (150)
1500
3R200-B
0.11
200
20BC260
400
132 (175)
2000
3RB320-B
0.075
320
continued
Table 10 - AC Line Impedance Recommendations for PowerFlex 70 Drives (Continued)
Drive
Drive Catalog
Number
(1)
Volts
kW (Hp)
Max Supply
kVA
(2)
3% Line Reactor
Open Style 1321-
Reactor Inductance
(mH)
Reactor Current
Rating (amps)
(3)