Chapter 6 Configure and Start Up the LDL-Series Linear Motor

8. Click the Tune tab.

9. Configure the parameters in the Tune tab as suggested in the

Initial Setting column. Leave all other tune options off for your
first pass. If necessary, reduce the Velocity Loop Proportional
Gain to maintain stability.

WARNING

Large Position Error Tolerances, such as those calculated
by the Auto Tune function in RSLogix 5000 programming
software, or when configuring a new axis with RSLogix
5000 software, can lead to undetected and repetitive
high energy impacts against axis end stops if proper
precautions are not in place. These tolerances can also
lead to undetected and repetitive high energy impacts
against unexpected obstructions. Such impacts can lead
to equipment damage and/or serious injury.

To identify the safety concerns that you have with
default Position Error Tolerance or after an Auto-Tune
Function, go to the

Rockwell Automation Knowlegebase

.

Click Find Technical Support Answers and search for
Answer Id 55937.

Parameter

Initial Setting

Units

Note

Travel Limit

100

mm

Suggested

Speed

250 mm/sec

Torque/Force

50 %

Rated

Direction

Forward Bi-directional

Damping Factor

0.8

(default)