Connecting wiring for your module – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 24

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

24 Installing the XM-440 Master Relay Module

Use the following steps to install the terminal base on a wall or panel.

1. Lay out the required points on the wall/panel as shown in the drilling

dimension drawing below.

2. Drill the necessary holes for the #6 self-tapping mounting screws.

3. Secure the terminal base unit using two #6 self-tapping screws.

4. To install another terminal base unit, retract the side connector into the

base unit. Make sure it is fully retracted.

5. Position the terminal base unit up tight against the neighboring terminal

base. Make sure the hook on the terminal base slides under the edge of
the terminal base unit.

6. Gently push the side connector into the side of the neighboring terminal

base to complete the backplane connection.

7. Secure the terminal base to the wall with two #6 self-tapping screws.

Connecting Wiring for Your
Module

Wiring to the module is made through the terminal base unit on which the
module mounts. The XM-440 is compatible only with the XM-942 terminal
base unit, Cat. No. 1440-TB-C.

Side Connector

Advertising