Invalid configuration errors – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 60

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

60 DeviceNet Information

Example

To save the configuration parameters to the non-volatile memory (EEPROM),
fill in the Class Instance Editor as shown below.

Invalid Configuration Errors

A Start or Save service request to an XM module may return an Invalid Device
Configuration error when there is a conflict amongst the configuration
settings.

The general error code for the Invalid Device Configuration error is D0

hex

. An

additional error code is returned with the general error code to specify which
configuration settings are invalid. The table below lists the additional error
codes associated with the Invalid Device Configuration error.

Select the Save

service code

Clear Send the attribute
ID and then enter the
Class (320

hex

) and

Instance (1)

Click Execute to
initiate the
action

Additional Error Codes returned with the Invalid Device Configuration Error (0xD0)

Error Code
(Hex)

Description

01

No specific error information is available.

02

Mismatched transducer, channel, and/or measurement unit.

03

Inverted transducer fault high/low values.

04

Alarm thresholds conflict with the alarm condition.

05

Alarm speed range is invalid.

06

Band minimum frequency is greater than maximum frequency. Or,
maximum frequency is greater than FMAX.

07

Relay is associated with an alarm that is not enabled.

08

Tachometer must be enabled for alarm or channel settings.

09

A senseless speed range is enabled on a speed alarm.