Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 47

Advertising
background image

Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

Configuration Parameters 47

Determines whether the relay is failsafe or
non-failsafe.

Failsafe operation means that when in alarm, the
relay contacts are in their “normal,” de-energized, or
“shelf-state” positions. In other words, normally
closed relays are closed in alarm, and normally open
relays are open in alarm. With failsafe operation, a
power failure equals an alarm.

The following are true of a relay in failsafe
operation:

• The relay is energized when power is applied to

the module.

• The relay in a nonalarmed condition has power

applied to the coil.

• In alarm condition, power is removed from the

relay coil, causing the relay to change state.

For non-failsafe operation, the following are true:

• Under nonalarm conditions, the relay closes the

circuit between the common and the N.C.
(normally closed) terminals.

• Under alarm conditions, the relay changes state to

close the circuit between the common and the
N.O. (normally open) terminals.

For failsafe operation, the following are true:

• Under nonalarm (with power applied to the unit)

conditions, the relay closes the circuit between the
common and the N.O. terminals.

• Under alarm or loss-of-power conditions, the relay

changes state to close the circuit between the
common and the N.C. terminals.

Sets the relay activation logic. Enter or select the
number of Input List entries (alarms and relays) that
must be active before the XM-440 relay will activate.

For example, there is one alarm and one relay in the
Input List and you set the Activate relay when
(Logic) parameter to "1." The module will activate
the relay when either the alarm in the list meets or
exceeds the selected Alarm Status condition(s) or
the relay in the list is activated.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Failsafe Relay

Failsafe
Option

XM Configuration
Utility

EDS File

Check means
failsafe

Failsafe

Clear means
non-failsafe

Nonfailsafe

XM Configuration
Utility

EDS File

Activate relay
when any n of n
inputs are
activated.

Logic